Show ApplicationProcessingDetails

Id: 20975043
Approve: false
Approve Note:
Clarification: false
Clarification Note:
Date Created: 2023-01-24 16:07:31.295
File Note: <p class="Default" style="margin-left: .25in; text-align: justify; line-height: 115%;"><span lang="EN-US" style="font-size: 11.0pt; line-height: 115%; font-family: 'Bookman Old Style','serif'; mso-fareast-font-family: Cambria; mso-bidi-font-family: Cambria; color: windowtext; mso-ansi-language: EN-US; mso-bidi-language: AR-SA;">During visit on 04/01/2023, effluent samples were collected from inlet and outlet of STP and submitted to Head Office, Water Lab, Patiala for analysis. As per analysis report received from lab, all the parameters are within prescribed limits i.e. pH - 7.7 against the prescribed limit of 6.0 &ndash; 8.5, BOD &ndash; 10 mg/l against the prescribed limit of 30 mg/l, TSS &ndash; 15 mg/l against the prescribed limit of 100 mg/l and F.coli &ndash; 680 MPN/100ml against the prescribed limit of 1000 MPN/100ml (analysis report attached).</span></p>
Inspection: false
Inspection Note:
Officer: PPCB134
Reject: false
Reject Note:
Role: RO AEE Rubal Goyal