| File Note: |
• It is intimated that the project is a Small scale Orange category Commercial project covered under Category 2091- Area/Infrastructure Development Project including educational institutions, community hall, IT Park, Theme park (Not covered under EIA notification 2006).
• Earlier, the project proponent was granted Consent to Establish' (NOC) under Water Act, 1974 & Air Act, 1984 Vide No. CTE/Fresh/JAL2/2024/24736922 dated 05/03/2024 valid upto 23/01/2025 for establishment of Commercial shops (G+2) @33 Numbers/day and discharge of domestic effluent @12.0 KLD with suitable conditions mentioned therein.
• Now, the project proponent has applied for fresh consent to operate under the Water (Prevention and Control of Pollution) Act, 1974 & Air (Prevention & Control of Pollution) Act, 1981 through OCMMS of the Board with requisite documents.
• The project proponent has deposited Rs. 120000/-, Rs. 24000/- as Other, NOC Fee and Rs. 500 as Form fee vide UTR/Reference No. 439476529 dated 26.12.2025 Under Water Act, 1974 and Rs. 120000/- vide UTR/Reference No. 738025529 dated 26.12.2025 Under Air Act, 1981, which is adequate upto 30.09.2030.
• The project site was visited by Er. Jatinder Soni, EE and Er. Rajinder Singh, AEE on 09.01.2026 and it was observed as under:-
1. During visit it is observed that one commercial shop (G+2) has been completed and civil work of commercial shops (G+1) @32 Numbers has also been completed. Construction of second floor of 32 commercial shops is underway. A McDonald’s drive-through has been started within the project premises.
2. The Project proponent has installed STP of Capacity 20 KLD based on MBBR technology which is principally adequate.
3. Out of the total treated effluent (~12 KLD), about 4.8 KLD will be reused internally for flushing purposes via a dual plumbing system and the remaining effluent (~7.2 KLD) will be discharged in an adequate green area measuring 0.5465 acres.
4. The Project Proponent has installed one D.G set of capacity 500 KVA with canopy and adequate stack height.
Keeping in view of above, it is recommended that fresh consent to operate under Water (Prevention & Control of Pollution) Act, 1974 may be granted to the colony upto 30.09.2030 with suitable special conditions please.
(Competency - Chief Environmental Engineer, Jalandhar)
|