File Note: It is submitted that Density of HSD= 0.84kg/L As told by industry representative , fuel consumption in 1 boiler= approximately 2litres/hour Total fuel consumption= 1.68kg/hour As per BS-6 norms, sulphur content of HSD= 10ppm= 0.001% Sulphur fraction= percentage sulphur in fuel/100= 0.00001 SO2 emissions= fuel consumption(kg/hour)X Sulphur fractionX64/32= 0.00003kg/hour Stack height required as per CPCB formula= H= 14Q(power0.3) =0.56metres Stack height required for 3 boilers with common stack= 3X0.56= 1.68metres Hence the stack height provided by industry is adequate. Submitted please