Show WasteManagementProcessingDetails

Id: 26015198
Application For: BMW
Application Id: 25873224
Approve: false
Approve Note:
Clarification: false
Clarification Note:
Date Created: 2024-06-25 11:43:03.457
File Note: 1. The HCF has installed the ETP-cum-STP comprising of components, collection tanks cum settling tanks  chemical and sodium hypo-chloride dosing  reaction tank  clarifier  primary tube settler  Aeration Tank  secondary tube settler  sump  carbon and sand filter. The treatment facility is operational during visit, however, there was no discharge at outlet due to lack of effluent. 2. The record regarding operation of ETP-cum-STP is being maintained by the HCF. 3. The HCF has installed the ETP-cum-STP of capacity 20 KLD and at present, the effluent generation is around 5 KLD due to new start of the HCF and less occupancy. The ETP-cum-STP installed by the HCF is adequate as compare to the proposed discharge by the HCF. 4. The HCF has also got analyzed its Bio Assay samples and as per the analysis report, Bio Assay is 90%. The copy of the report enclosed. Further, the concentration of various parameters of the treated effluent got analyzed by the HCF is pH = 7.42, TSS = 10 mg/l, TDS = 1042 mg/l, COD = 24 mg/l, BOD = 4 mg/l, Oil & Grease < 3 and Bio Assay is 90%. The above all parameters are within the permissible limit of the Board. 5. The HCF has also provided the separate storage room for the storage of its bio-medical waste and further lifting to the CBWTF, inadvertently it was typed as TSDF instead of CBWTF. 6. The HCF is segregating the Bio-Medical Waste as per BMW Rules, 2016 and using bar code stickers. Keeping in view of above, if approved, the HCF may be granted fresh authorization upto 31.03.2029 under BMW Rules, 2016 with suitable conditions and with special conditions that: 1. This authorization is valid for 45 Beds only. HCF will apply for CTO/CTE if it increases its bed capacity. 2. The HCF will comply with the provisions of the BMW Rules, 2016, the Water Act, 1974 and the Air Act, 1981 in true letter & spirit. 3. The HCF will renew its agreement with the CBWTF for lifting of its BMW before expiry of the same. 4. The HCF will submit Annual Report on Bio-Medical Waste Management in Form-IV by 30th June every year. 5. The HCF will maintain proper record of generation and lifting of bio-medical waste. 6. The HCF shall got lifted/handed over its Bio-Medical Waste generated to the Common Bio-Medical Waste Treatment Facility on daily basis. 7. The HCF shall obtain other statutory approvals required from other departments, if any. 8. The HCF shall operate its ETP-cum-STP properly and adequately and shall achieve the prescribed effluent discharge standards. Competency Environmental Engineer
Inspection: false
Inspection Close: false
Inspection Close Note:
Inspection Note:
Last Updated: 2024-06-25 11:43:03.457
Officer: PPCB088
Officer Fwd: PPCB082
Reject: false
Reject Note:
Role: RO AEE Jaspal Singh
Role Fwd: RO EE Guneet Sethi